Criterios de diseño de envolvente higrotérmica libre de moho
| dc.contributor.advisor | Bobadilla Moreno, Luis Ariel | es |
| dc.contributor.author | Reyes Riveros, Alejandro Enrique | |
| dc.contributor.editor | Universidad del Bío-Bío. Facultad de Arquitectura, Construcción y Diseño (Chile) | es |
| dc.date.accessioned | 2023-01-18T15:24:58Z | |
| dc.date.available | 2023-01-18T15:24:58Z | |
| dc.date.issued | 2020 | |
| dc.description | Tesis (Magíster en Hábitat Sustentable y Eficiencia Energética) --Universidad del Bío-Bío. Concepción, 2020. | es |
| dc.description.abstract | El moho presente en los materiales de una vivienda provoca daños y deterioro en los elementos que la componen y puede perjudicar la salud del individuo que la habita. Todas las decisiones y actividades de diseño en la construcción y gestión afectan el riesgo de crecimiento del moho. Es así que se hace necesario conocer la naturaleza del microorganismo moho y del material sobre el cual se formará, además de los factores dentro del entorno de las condiciones ambientales fluctuantes en el que se encuentra. La normativa nacional existente no ha logrado limitar la formación de moho, en una encuesta realizada en Temuco y Padre Las Casas se determinó que la mitad de las viviendas encuestadas presentaban problemas de postventas relacionadas con la humedad y casi un cuarto reportó problemas de deterioro y manchas en los revestimientos de pinturas y papel mural. Se requiere un mayor desarrollo de las normativas y el establecimiento de criterios que permitan el diseño de una envolvente higrotérmica libre de moho. Los nuevos requerimientos de eficiencia energética contenidos en el PDA podrían empeorar la situación actual además de dejar obsoletos algunos sistemas constructivos. La normativa internacional, el estado del arte y las herramientas de cálculo dinámico de condensaciones y formación de moho pueden ayudar a definir estos criterios de diseño. En esta investigación se experimenta con un elemento muro tipo estándar PDA y se evalúa con 4 diferentes sustratos de revestimiento interior: esmalte al agua común (EAC), papel mural vinilizado (PMV), esmalte al agua antimoho (EAA) y papel mural común (PMC). Sobre estos 4 casos se realizan cálculos teóricos y experimentos prácticos en laboratorio que permitan determinar el riesgo de condensaciones y formación de moho. El cálculo estático se realiza con el método Glaser, según NCh1973:2014 y en base a una herramienta diseñada por la DITEC. El cálculo dinámico se realiza con los softwares WUFI Pro, WUFI Bio y WUFI VTT. El experimento se realiza en la cámara de clima controlado del laboratorio CITEC de la Universidad del Bío Bío en la ciudad de Concepción, Chile. Los resultados obtenidos se comparan entre los diferentes cálculos, experimento, normativas existentes y el estado de arte relacionado. El análisis y discusión de los resultados incluye un análisis de sensibilidad y una posible modelación estadística predictiva de la formación de moho. El revestimiento EAC es el caso que alberga menos agua. El EAA por su parte es el que resulta con mayor contenido de agua, tanto en la solución constructiva total como en la capa subyacente (el yeso cartón). El contenido de agua de la capa subyacente y su fluctuación en el tiempo dependen directamente del tipo de revestimiento de terminación elegido. Los cálculos dinámicos y experimento en laboratorio además coinciden en que las fluctuaciones en el contenido de agua del EAC son las menos variables y las del EAA, seguidas del PMV son las más acentuadas. Lo anterior permite concluir que el EAC permite un secado más rápido o bien frena el vapor de agua de tal manera que sus fluctuaciones de contenido de agua son menos acentuadas. A pesar de las fluctuaciones más acentuadas, el revestimiento EAA es el que presenta un mejor desempeño frente a la formación de moho y por el contrario el revestimiento EAC es el de peor desempeño. Esto es consecuente entre los resultados de curva de isopletas, tasa e índice de crecimiento de moho. La comparación de los casos de revestimientos y variaciones evaluadas permite concluir que la principal causa de formación de moho se basa en los valores elevados de humedad relativa interior, luego el siguiente caso sería el tipo de revestimiento existente, su origen y sensibilidad. Los cálculos realizados entones demuestran la importancia de dos pilares fundamentales para una envolvente libre de moho: el ambiente interior y el sustrato. | es |
| dc.description.abstract-2 | Mould present in the materials of a house causes damage and deterioration in the elements that compose it and can harm the health of the individual who lives there. All design decisions and activities in construction and management affect the risk of mold growth. Thus, it is necessary to know the nature of the mould microorganism and the material on which it will form, as well as the factors within the environment of the fluctuating environmental conditions in which it is found The existing national regulations have not been able to limit the formation of mould, in a survey carried out in Temuco and Padre Las Casas it was determined that half of the surveyed dwellings presented post-sale problems related to humidity and almost a quarter reported problems with deterioration and stains in paint and wallpaper coatings. Further development of regulations and the establishment of criteria to enable the design of a mould-free hygrothermal envelope is required. The new energy efficiency requirements contained in the PDA could worsen the current situation, in addition to rendering some construction systems obsolete. International standards, the state of the art and dynamic calculation tools for condensation and mould formation can help to define these design criteria. In this research, a standard PDA-type wall element is experimented with and evaluated against 4 different interior cladding substrates: common water-based paint (EAC), vinyl wallpaper (PMV), water-based anti-mould paint (EAA) and common wallpaper (PMC). Theoretical calculations and practical laboratory experiments are carried out on these 4 cases to determine the risk of condensation and mould formation. The static calculation is made with the Glaser method, according to NCh1973:2014 and based on a tool designed by DITEC. The dynamic calculation is carried out with the software WUFI Pro, WUFI Bio and WUFI VTT. The experiment is carried out in the climate controlled chamber of the CITEC laboratory at the University of Bío Bío in the city of Concepción, Chile. The results obtained are compared between the different calculations, experiment, existing regulations and the related state of the art. The analysis and discussion of the results include a sensitivity analysis and a possible predictive statistical modeling of mold formation. The EAC coating is the least water-bearing case. The EAA is the case with the highest water content, both in the total building solution and in the underlying layer (the plasterboard). The water content of the underlying layer and its fluctuation over time depend directly on the type of finishing plaster chosen. Dynamic calculations and laboratory experiments further agree that the fluctuations in water content of EAC are the least variable and those of EAA, followed by PMV, are the most pronounced. This leads to the conclusion that EAC allows faster drying or slows down water vapor so that its water content fluctuations are less accentuated. In spite of the more pronounced fluctuations, the EAA coating is the best performer against mold formation, while the EAC coating is the worst performer. This is consistent between the results of the isopleth curve, rate, and rate of mold growth. The comparison of the cases of coatings and variations evaluated allows us to conclude that the main cause of mould formation is based on the high values of interior relative humidity, then the next case would be the type of existing coating, its origin and sensitivity. The calculations made then demonstrate the importance of two fundamental pillars for a mould-free envelope: the indoor environment and the substrate. It can be seen that a higher equivalent air thickness (Sd) value does not guarantee low mould growth, as the graphs show that the higher the Sd value, the higher the mould index and growth rate (IC and RC) value. The higher the Sd, the higher the water content. | en |
| dc.description.call-number | T(E) 720.47 R33 2020 | es |
| dc.identifier.uri | http://repobib.ubiobio.cl/jspui/handle/123456789/3870 | |
| dc.language.iso | es | es |
| dc.subject | FORMACION DE MOHO | es |
| dc.subject | CONDENSACION SUPERFICIAL | es |
| dc.subject | PATOLOGIAS VIVIENDAS | es |
| dc.subject | SUSTRATO | es |
| dc.subject | SIMULACION HIGROTERMICA DINAMICA | es |
| dc.title | Criterios de diseño de envolvente higrotérmica libre de moho | es |
| dc.type | Tesis | es |