Publicación: STUDY OF REACTIVE POWER COMPENSATION CAPABILITIES AND LC FILTER DESIGN FOR A THREE-PHASE CURRENT-SOURCE STATCOM

Fecha
2018
Título de la revista
ISSN de la revista
Título del volumen
Editor
IEEE INTERNATIONAL CONFERENCE ON AUTOMÁTICA (ICA-ACCA)
Resumen
THIS WORK SHOWS THE USE OF THE OPERATING REGION OF A D-STATCOM BASED ON CURRENT-SOURCE INVERTERS TO DEFINE ITS OPERATING POINT AND ITS LC FILTER. FIRST, A CURRENT-SOURCE STATCOM MODEL IS DEFINED TO COMPUTE ITS OPERATING REGION AND OBTAIN A RELATION BETWEEN REACTIVE POWER COMPENSATION AND THE DEVICE POWER LOSSES. BECAUSE THIS RELATIONSHIP DEFINES THE LOSSES COSTS OF THE REACTIVE POWER COMPENSATION, THIS RELATION IS USED TO DEFINE A METHODOLOGY TO GET AN OPERATING POINT AND DESIGN THE LC AS A FUNCTION OF THE DESIRED COST FOR NOMINAL POWER COMPENSATION. THE METHODOLOGY IS TESTED IN THE DESIGN OF A 125KVA/380V DISTRIBUTION GRID, WHERE SIMULATION RESULTS CORROBORATE THE ANALYSIS, INCLUDING CHANGES FROM ONE OPERATING POINT TO ANOTHER, IN OPEN LOOP, TO SHOW THE COMPENSATION CAPABILITIES, THE POWER TOPOLOGY EFFORT AND THE GRID MAINS VARIABLES WITH COMPENSATION.
Descripción
Palabras clave
STATCOM, power quality, CURRENT SOURCE CONVERTER